2023-04-17 11:30:20JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND
 SEALED ENGINEERED DESIGN PROCEDURE DRAWINGS BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT, OR REGISTERED ROOF CONSULTANT. BASED ON THE
 DIMENSIONS OF THE STRUCTURE, APPROPRIATE WIND LOADS ARE
 DETERMINED USING CHAPTER 16 OF THE FLORIDA BUILDING
 CODE 2020 FOR ROOF CLADDING WIND LOADS. THESE COMPONENT
 WIND LOADS FOR ROOF CLADDING ARE COMPARED TO THE
 ALLOWABLE PRESSURE LISTED ABOVE. THE DESIGN
 PROFESSIONAL SHALL SELECT THE APPROPRIATE ERECTION
 DETAILS TO REFERENCE IN HIS DRAWINGS FOR PROPER
 FASTENER ATTACHMENT TO HIS STRUCTURE AND ANALYZE THE
 PANEL FASTENERS FOR PULLOUT. SUPPORT FRAMING MUST BE IN
 COMPLIANCE WITH FLORIDA BUILDING CODE 2020 CHAPTER 22
 FOR STEEL, AND CHAPTER 16 FOR STRUCTURAL LOADING.
 PLEASE REFERENCE PRODUCT APPROVAL FL9352.3- R5
 EVALUATION REPORT PAGES #1-#5 FOR REQUIRED DATA TO MEET
 COMPLIANCE.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN
 ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  