2023-05-05 12:29:47 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 THE CITY OF WEST PALM BEACH IS NOT |
| LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. PROVIDE |
| A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| USED. INCLUDE COVER PAGE, EVALUATION REPORTS, |
| LIMITATIONS PAGE AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. GENERAL LIMITATION #7 IS SPECIFICALLY |
| REFERRED TO IN THIS NOA. SUBMIT FASTENER DENSITY |
| CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, |
| OR REGISTERED ROOF CONSULTANT. NOTE: THIS PROJECT IS |
| LOCATED IN AN EXPOSURE CATEGORY C AREA. |
| 2. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT |
| COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL |
| AND CHAPTER 11 OF THE 2020 FBC-PLUMBING. |
| 3. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART |
| OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS |
| BY YOUR BUILDING INSPECTOR. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |