2023-06-26 13:28:14 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT AN ORIGINAL DIGITALLY SIGNED COPY OF THE |
| TECHNICAL SPECIFICATIONS FOR THE CHILLER EQUIPMENT. THE |
| DIGITAL SIGNATURE ON THE ONE THAT WAS SUBMITTED COULD |
| NOT BE VERIFIED. ELECTRONICALLY SUBMITTED DRAWINGS ARE |
| REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL |
| SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC |
| 61G15 |
| |
| 2) ALTHOUGH THIS IS NOT A THRESHOLD BUILDING, IF YOU |
| WISH TO USE A THRESHOLD INSPECTOR TO DO THE STRUCTURAL |
| INSPECTIONS, THEN YOU WILL NEED TO SUBMIT THE REQUIRED |
| THRESHOLD INSPECTION DOCUMENTS. |
| |
| A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| |
| C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| |
| D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. |
| |
| F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE. |
| |
| G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| CEILINGS. |
| |
| J) SUBMIT THE CITY OF WEST PALM BEACHES THRESHOLD |
| INSPECTOR DOCUMENTS. PLEASE CONTACT ME WITH AN EMAIL |
| ADDRESS AND I WILL BE HAPPY TO SEND YOU A COPY OF THE |
| CURRENT (OCTOBER 2018) GUIDELINES AND POLICIES FOR |
| PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND |
| RESIDENT INSPECTORS. |
| |
| 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR |
| DOOR TYPES. INDICATE THE SPECIFIC ITEMS AND THEIR |
| DESIGN PRESSURES BY HI-LIGHTING OR CIRCLING THEM IN THE |
| PRODUCT APPROVALS. THESE ITEMS CAN BE DEFERRED IF |
| REQUESTED AND LISTED ON THE PLANS, HOWEVER, THE |
| DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE |
| BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. THESE |
| ITEMS CAN BE DEFERRED IF REQUESTED AND LISTED ON THE |
| PLANS. |
| |
| 4) THE CHILLER MODULE DOCUMENTS ARE REQUIRED TO BE |
| SUBMITTED FOR REVIEW AND APPROVAL BY THIS OFFICE AFTER |
| THEY HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. THE MODULES WILL BE REQUIRED TO |
| MEET THE WIND LOADS FOR THE PROJECT. FBC 1603.1 |
| |
| 5) A PERMIT OR SUB-PERMIT FROM A CBC OR A CGC WILL BE |
| REQUIRED TO PERFORM THE STRUCTURAL WORK FOR THIS |
| PROJECT. FBC 105.1 |
| |
| 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |