Plan Review Notes
Plan Review Notes For Permit 23040116
Permit Number 23040116
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-04-05 15:57:36TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/
 DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR
 LEAKS
 & INSPECTOR DRAIN AFTER 2 HRS)
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved