Plan Review Notes For Permit 23031983 |
Permit Number |
23031983 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-06-30 11:33:09 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. REVIEW ELECTRICAL RISER PRESENTED FOR CORRECT | | GROUNDED ELECTRICAL CONDUCTOR (GEC) PER NEC TABLE | | 250(C)(1) AND INDICATE THE MINIMUM SIZES FOR THE | | EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250.122. | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN P. PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | 561-805-6738 | | [email protected] | | |
|