Plan Review Notes
Plan Review Notes For Permit 23031933
Permit Number 23031933
Review Stop E
Sequence Number 1
Notes
Date Text
2023-04-26 14:55:36ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE THE UPSTREAM 600 AMP PANEL LOAD
 CALCULATION AND PANEL SCHEDULE IN ACCORDANCE WITH NEC
 215.5
 2)
 215.5 DIAGRAMS OF FEEDERS.
 IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A
 DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR
 TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM
 SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING
 DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO
 BE USED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  