Plan Review Notes
Plan Review Notes For Permit 23031726
Permit Number 23031726
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-28 12:43:40*****AFTER RECEIVING INFORMATION REGARDING THIS EVENT
 WITH PD TRAFFIC CONTROL, I HAVE PASSED MY REVIREW*****
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THOUGH THE TENT ITSELF IS NOT REQUIRED BY FLORIDA
 STATUTE TO BE REVIEWED FOR LIFE SAFETY, THE TENT
 APPEARS TO BE LOCATED WITHIN THE RODWAY.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 DOES THE EVENT HAVE AN APPROVED MOT FOR THE ROD
 CLOSURE?
  
 CAN YOU PLEASE PROVIDE IT?
  
  
  
 2) WHAT IS THE PURPOSE OF TENT?
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 IS THERE AN APPPROVED EVENT PERMIT THROUGH THE CITY?
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  