2023-05-05 14:47:021ST REVIEW FMC
 PERMIT: 23031690
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT.
 FEC C403.2.1
  
 2) WE HAVE NO RECORDS OF A PERMITTED MECHANICAL SYSTEM
 FOR THIS ADDRESS. PROVIDE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS FOR THIS PROJECT. FEC C403.2.1
  
 3) THE EXHAUST FAN SCHEDULE SHOWS A NOTE 1 UNDER NOTES,
 THERE IS NO NOTE ONE IN THE SCHEDULE. PROVIDE THE NOTE
 FOR THIS EXHAUST FAN. THE 60 CFMS OF EXHAUST IS BASED
 ON CONTINUOUS USE WHILE OCCUPIED. PLEASE SHOW THIS FOR
 THE BATH EXHAUST FAN. FMC TABLE 403.3.1.1
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS SPACE.
 FMC 403.3.1.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  