2023-04-07 16:17:09 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 23031665 | | 4/7/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 007 PLUMBING LAYOUT: THE STORM WATER DRAINAGE | | AND POOL OVERFLOW DRAINAGE VIA THE FLOOR DRAIN ON THE | | OPEN 2ND FLOOR DECK SHALL NOT DISCHARGE INTO THE | | SANITARY SYSTEM IN ACCORDANCE WITH SEC. 90-126 ITEM #5 | | WPB CODE OF ORDINANCES. PLEASE SHOW THE DISPOSAL | | LOCATION OR PLACE A NOTE ON THE PLANS. | | | | 2) SHEET 2: THE PIPING SCHEMATIC AND THE TDH | | CALCULATION DO NOT MATCH THE PIPING LAYOUT ON 007 WHICH | | SHOWS TWO MAIN DRAINS AND TWO DRAIN LINES FROM THE POOL | | CONNECTING TO A TEE. PLEASE REVISE AND SHOW THE SIZE OF | | THE DRAIN PIPE FROM THE TEE TO THE RECIRCULATION | | EQUIPMENT- SEC. R4501.6.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|