2023-04-07 16:17:091ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23031665
 4/7/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 007 PLUMBING LAYOUT: THE STORM WATER DRAINAGE
 AND POOL OVERFLOW DRAINAGE VIA THE FLOOR DRAIN ON THE
 OPEN 2ND FLOOR DECK SHALL NOT DISCHARGE INTO THE
 SANITARY SYSTEM IN ACCORDANCE WITH SEC. 90-126 ITEM #5
 WPB CODE OF ORDINANCES. PLEASE SHOW THE DISPOSAL
 LOCATION OR PLACE A NOTE ON THE PLANS.
  
 2) SHEET 2: THE PIPING SCHEMATIC AND THE TDH
 CALCULATION DO NOT MATCH THE PIPING LAYOUT ON 007 WHICH
 SHOWS TWO MAIN DRAINS AND TWO DRAIN LINES FROM THE POOL
 CONNECTING TO A TEE. PLEASE REVISE AND SHOW THE SIZE OF
 THE DRAIN PIPE FROM THE TEE TO THE RECIRCULATION
 EQUIPMENT- SEC. R4501.6.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  