2023-07-13 15:37:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM |
| OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO |
| MANUFACTURE SPECIFICATION SHEETS TO VERIFY COMPLIANCE |
| WITH NFPA CODES. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| SPEC SHEETS OF THE PROPOSED. |
| |
| |
| |
| 2) THERE IS AN INDICATION OF A VENTLESS HOOD SYSTEM |
| OVER COOKING EQUIPMENT, HOWEVER, THERE IS NO |
| INDICATIONS COMPLIANCE WITH NFPA 96 AND THE CONTROL AND |
| EXTINGUISHMENT OF GREASE LADEN VAPORS. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PLEASE PROVIDE A HOOD AND SUPPRESSION SYSTEM PER NFPA |
| 96 OR PROVIDE DETAILED JUSTIFICATION AND FIRE CODE |
| REFERENCES WHY IS IS NOT REQUIRED FOR THIS COMMERICIAL |
| HOOD SYSTEM. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |