Plan Review Notes
Plan Review Notes For Permit 23031575
Permit Number 23031575
Review Stop M
Sequence Number 2
Notes
Date Text
2023-04-13 06:54:09SHEET A0.4 IS STILL SHOWING THE 1-HOUR RATED WALLS FOR
 TENANT SEPARATION. SHEET M1.2 IS MISSING THE FIRE
 DAMPERS PROTECTING THE PENETRATIONS AT THE MAIN DUCTS
 AND THE RETURN AIR BOXES IN THE RATED WALLS. FMC 607
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  