Plan Review Notes
Plan Review Notes For Permit 23031575
Permit Number 23031575
Review Stop M
Sequence Number 1
Notes
Date Text
2023-03-29 13:49:181ST REVIEW FMC
 PERMIT: 22080521
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0.4 INDICATES THE WALLS IN THE LOBBY ARE 1
 HOUR RATED. SHEET M1.2 DOES NOT HAVE THE REQUIRED FIRE
 DAMPERS WHERE THE MAIN TRUNK LINE PENETRATES THESE
 WALLS. PLEASE SHOW THE REQUIRED FIRE DAMPERS AT THESE
 PENETRATIONS. FMC 607.5.3
  
 2) PLEASE REFRESH MY MEMORY, THERE ARE 3 SYMBOLS IN THE
 EXIT PASSAGEWAY CEILING. WHAT ARE THESE SYMBOLS? WHY
 ARE THEY IN THE RATED CEILING OF THIS EXIT PASSAGEWAY?
  
 3) SHEET A0.4 INDICATES THE WALLS SEPARATING THE TENANT
 SPACES FROM THE CORRIDOR ARE ALSO 1 HOUR RATED WALLS.
 PLEASE PROVIDE THE FIRE DAMPERS REQUIRED FOR THE
 PENETRATIONS IN THESE WALLS. FMC 607.5.3
  
 4) SHOW ON SHEET M1.2 THAT THE VAV???S WILL BE SHUT
 DOWN IN THE CASE OF SMOKE. FMC 606.2.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  