Plan Review Notes
Plan Review Notes For Permit 23031549
Permit Number 23031549
Review Stop B
Sequence Number 2
Notes
Date Text
2023-06-06 17:02:36PREVIOUS COMMENTS NOT ADDRESSED.
  
 DRAIN ON SHOWER SECTION IS SHOWING IN THE MIDDLE OF
 SHOWER ALTHOUG NOTE ON PLAN SAY YOU ARE RE-USING THE
 SAME DRAIN LOCATION.
 SHOWER NEED TO BE MIN 36" WIDE IN DEPTH REFER TO FHA
 DESIGN GUIDELINE- THE 30"X48" TEMPLATE IS CORRECT BUT
 ONCE THE WIDTH OF THE SHOWER IS CORRECTED YOU WILL NOT
 HAVE THE CLEARANCE.
 OTHER OPTION IS TO SIGN THE AFFIDAVIT AS INDICATED IN
 PREVIOUS COMMENTS.
  
 DO NOT HESITATE TO CONTACT ME IF YOU HAVE ANY QUESTIONS
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II