2023-04-19 10:26:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF THE INSTALLATION OF |
| LAMINATE, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE |
| ACTUAL PROPOSED LAMINATE FLOORING. |
| |
| LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD BUT |
| NOT ALL ARE TESTED AND MEETING LISTED AND NFPA |
| STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LAMINATE |
| FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE IS INDICATIONS OF DROP CEILINGS THAT AMY |
| AFFECT FIRE SPRINKLER COVERAGE AND LOCATIONS THAT WILL |
| REQUIRE MODIFICATIONS. |
| |
| THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| |
| ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| DRAWINGS. |
| |
| |
| |
| WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |