2023-05-24 12:05:16 | 2ND PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. VENTS ADDED |
| |
| 2. VENTS ADDED |
| |
| 3. NOT ADDRESSED CORRECTLY - THE VENT NEEDS TO CONNECT |
| TO THE FIXTURE DRAIN ITSELF OR THE FIXTURE DRAIN NEEDS |
| TO CONNECT TO THE BATHROOM GROUP'S PIPING. |
| MASTER BATH-1 -- 2020 FRC P3101.2.1 - THE SHOWER IS NOT |
| VENTED. IT CANNOT CONNECT TO A HORIZONTAL BRANCH |
| WITHOUT A VENT. |
| |
| 4. NOT ADDRESSED |
| 2020 FRC P2902.5 - THE BACKFLOW YOU'VE SHOWN AT THE |
| HOUSE WOULD BE REQUIRED AT THE STREET CONNECTION. ALSO, |
| THE POOL FILLER AND THE IRRIGATION WOULD ALSO REQUIRE |
| INDIVIDUAL BACKFLOW PREVENTERS. |
| |
| 5. .NEW COMMENT - LAVS ARE NOW MISSING FROM THE DRAWING |
| IN MASTER BATH 1 |
| |
| 6. NEW COMMENT - OUTDOOR SINK IS NOW MISSING FROM THE |
| DRAWING. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |