Plan Review Notes
Plan Review Notes For Permit 23031544
Permit Number 23031544
Review Stop P
Sequence Number 2
Notes
Date Text
2023-05-24 12:05:162ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. VENTS ADDED
  
 2. VENTS ADDED
  
 3. NOT ADDRESSED CORRECTLY - THE VENT NEEDS TO CONNECT
 TO THE FIXTURE DRAIN ITSELF OR THE FIXTURE DRAIN NEEDS
 TO CONNECT TO THE BATHROOM GROUP'S PIPING.
 MASTER BATH-1 -- 2020 FRC P3101.2.1 - THE SHOWER IS NOT
 VENTED. IT CANNOT CONNECT TO A HORIZONTAL BRANCH
 WITHOUT A VENT.
  
 4. NOT ADDRESSED
 2020 FRC P2902.5 - THE BACKFLOW YOU'VE SHOWN AT THE
 HOUSE WOULD BE REQUIRED AT THE STREET CONNECTION. ALSO,
 THE POOL FILLER AND THE IRRIGATION WOULD ALSO REQUIRE
 INDIVIDUAL BACKFLOW PREVENTERS.
  
 5. .NEW COMMENT - LAVS ARE NOW MISSING FROM THE DRAWING
 IN MASTER BATH 1
  
 6. NEW COMMENT - OUTDOOR SINK IS NOW MISSING FROM THE
 DRAWING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  