2023-04-11 06:03:16 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. BATH-2 -- 2020 FRC P3108.2.1 - NOT VENTED TO CODE. |
| THERE ARE 3 TRAPPED FIXTURES ON THE HIGH SIDE OF THE |
| VENTED FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT. |
| ONLY ONE IS ALLOWED ON THE HIGH SIDE OF THE VENTED |
| FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT. PLEASE |
| RECONFIGURE. |
| |
| 2. MASTER BATH-2 -- 2020 FRC P3108.2.1 - NOT VENTED TO |
| CODE. THERE ARE 2 TRAPPED FIXTURES ON THE HIGH SIDE OF |
| THE VENTED FIXTURE'S CONNECTION TO THE HORIZONTAL WET |
| VENT. ONLY ONE IS ALLOWED ON THE HIGH SIDE OF THE |
| VENTED FIXTURE'S CONNECTION TO THE HORIZONTAL WET VENT. |
| PLEASE RECONFIGURE. |
| |
| 3. MASTER BATH-1 -- 2020 FRC P3101.2.1 - THE SHOWER IS |
| NOT VENTED. IT CANNOT CONNECT TO A HORIZONTAL BRANCH |
| WITHOUT A VENT. |
| |
| 4. 2020 FRC P2902.5 - THE BACKFLOW YOU'VE SHOWN AT THE |
| HOUSE WOULD BE REQUIRED AT THE STREET CONNECTION. ALSO, |
| THE POOL FILLER AND THE IRRIGATION WOULD ALSO REQUIRE |
| INDIVIDUAL BACKFLOW PREVENTERS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| |