Notes |
Date |
Text |
2023-05-10 09:32:27 | PLAN REVIEWER: ED ROSEBERRY PX2909 | | EMAIL: [email protected] | | PH: 772-359-3502 | | | | 1. PLEASE SUBMIT SCHEDULE SHOWING LOCATION, MRH, AND | | WALL ZONE FOR REPLACEMENT FENESTRATION. THIS IS A | | LISTING OF PRODUCTS DESCRIBING UNIT 1, 2....ETC. FBC | | 107.2 | | 2. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT | | FENESTRATION, WITH SPECIFIC MODELS, SIZES, AND DESIGN | | PRESSURE TABLES HIGHLIGHTED. FBC 107.2 | | 3. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | FBC B 1405.4. ***NOTE*** THIS IS NOT USUALLY INCLUDED | | IN FBC/NOA. COMPLIANCE MUST BE SHOWN SEPARATELY. | | 4. PLEASE SUBMIT APPLICATION SHOWING COMPLETE SCOPE OF | | WORK. FBC 107.2 | | |
|