2023-04-06 17:00:25 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23031497 |
| 10221 BLUE HERON PT |
| |
| 1- GENERATOR CONCRETE PAD ENGINEERING SUBMITTED IS FOR |
| GENERAC AND KOHLER GENERATORS. GENERATOR SPECS |
| SUBMITTED ARE FOR A HONEYWELL GENERATOR. NEED TO |
| PROVIDE ENGINEERING FOR HONEYWELL GENERATORS. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE |
| ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL |
| SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. |
| ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| SIGNATURE. |
| |
| ENGINEERS |
| 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| 3- THE ENGINEER IS LIMITING THE USE OF THIS CONCRETE |
| PAD ENGINEERING TO A SPECIFIC LOCATION (ZIP CODE AND |
| COMPANY). ACCORDING TO THIS, THE CONCRETE PAD |
| ENGINEERING IS VOID BECAUSE THE LOCATION OF THIS |
| PROJECT DOESN'T MATCH THAT LIMITATION. PROVIDE |
| ENGINEERING FOR THIS SITE SPECIFIC LOCATION. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |