Plan Review Notes
Plan Review Notes For Permit 23031497
Permit Number 23031497
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-06 17:00:25RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23031497
 10221 BLUE HERON PT
  
 1- GENERATOR CONCRETE PAD ENGINEERING SUBMITTED IS FOR
 GENERAC AND KOHLER GENERATORS. GENERATOR SPECS
 SUBMITTED ARE FOR A HONEYWELL GENERATOR. NEED TO
 PROVIDE ENGINEERING FOR HONEYWELL GENERATORS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE
 ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL
 SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS.
 ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3- THE ENGINEER IS LIMITING THE USE OF THIS CONCRETE
 PAD ENGINEERING TO A SPECIFIC LOCATION (ZIP CODE AND
 COMPANY). ACCORDING TO THIS, THE CONCRETE PAD
 ENGINEERING IS VOID BECAUSE THE LOCATION OF THIS
 PROJECT DOESN'T MATCH THAT LIMITATION. PROVIDE
 ENGINEERING FOR THIS SITE SPECIFIC LOCATION. SEC.
 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  