2023-04-10 16:56:081ST REVIEW FBC-2020 PLUMBING
 PERMIT-23031460
 4/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A2 WHICH HAS THE PLUMBING RISER DRAWING IS NOT
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD-
 FL. STATUTE 481.221 & SEC. 61G1- 16.005 FAC.
  
 2) A2: PROVIDE A UL TESTED AND APPROVED FIRESTOPPING
 DETAIL FOR SEALING THE ANNULAR SPACE AROUND NEW DRAIN
 PIPE PENETRATION OF THE FLOOR SLAB- SEC. 315.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  