Plan Review Notes
Plan Review Notes For Permit 23031443
Permit Number 23031443
Review Stop G
Sequence Number 1
Notes
Date Text
2023-04-05 09:41:011ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 - THERE ISN'T A
 CORRESPONDING GENERATOR PERMIT. WHEN THE GENERATOR
 PERMIT IS APPLIED FOR, I CAN COMPLY THIS COMMENT. THE
 PLACEMENT OF THE GAS LINE IS RELATIVE TO THE SEPARATION
 DISTANCES REQUIRED AND REVIEWED IN THE GENERATOR PERMIT
 REVIEWS.
  
 2. 2017 WPB AMEND 107.3.5.3 (13) - PROVIDE A FLOOR PLAN
 THAT OVERLAYS THE GAS ROUTING WITH RESPECT TO THE FLOOR
 PLAN. SHOW LOCATIONS OF THE FIXTURES WITHIN THE FLOOR
 PLAN.
  
 3. 2017 WPB AMEND 107.3.5.3 (13) - INCLUDE ROOM SIZING
 AND COMBUSTION AIR CALCS FOR THE FIREPLACE AND RANGE.
  
 4. 2017 WPB AMEND 107.3.5.3 (13) - ON THE FLOOR PLAN,
 INCLUDE SEPARATION FROM STRUCTURE OPENINGS. GENERATORS
 ARE 10 FEET FROM OPENINGS, POOL HEATERS ARE 4 FEET FROM
 OPENINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved