Date |
Text |
2023-04-11 07:28:35 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND - 105.1 - I AM UNABLE TO LOCATE ANY |
| RECORDS SHOWING THE COMBINATION OF THE TWO UNITS. A |
| PERMIT IS REQUIRED TO CHANGE THE OCCUPANCY OF A SPACE. |
| PER THE 2020 EXISTING BUILDING CODE, SHOW THE INCREASED |
| OCCUPANCY LOAD AND THE CORRESPONDING FIXTURE |
| REQUIREMENTS TO BE MET PER 403.1 OF THE FLORIDA |
| PLUMBING CODE. |
| |
| 2. 2020 FEX 1010.3 I - IF THE NEW USE HAS GREASE LADEN |
| WASTE, A GREASE INTERCEPTOR WILL BE REQUIRED. |
| |
| 3. 2017 WPB AMENDS 107.2.1 - CLARIFY THE SCOPE OF WORK. |
| IT APPEARS THROUGH PERMIT HISTORY THAT YOU ARE ADDING |
| PLUMBING FIXTURES (TRIPLE SINKS, ICE BINS, HAND SINKS, |
| BATHROOMS). PLEASE CLARIFY THE SCOPE AND SHOW THE |
| INTENDED PLUMBING WORK TO BE DONE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |