2023-06-21 16:50:15BUILDING REVIEW COMMENTS:
 W.P.B. PERMIT:23051177
 REVIEWED: 6.23.2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
  
 SHEET A-1
  
 DESIGN CRITERIA UPDATE ROOFING MATERIAL TO FLAT ROOF
  
 SHEET A-2
  
  [A]109.1 UPDATED FEES, REFER TO COVER SHEET.
  
  ICC TABLE IS $167.37 PER S.F. FOR AREA UNDER AC VB
 CONSTRUCTION:
 YOU ARE ADDING 854 SF = $142,933.98
  ICC TABLE IS $66.48 PER S.F. FOR UTILITY OR
 MISCELLANEOUS: YOU ARE ADDING 100 S.F. =$ 6,648.00
  
  GRAND TOTAL PERMIT VALUE: $149,581.98
  
 WINDOWS AND DOORS SCHEDULE
  
  AS PER FBC 1030.2 EGRESS WINDOW MIN IS 5.7. S.F.
  WINDOW B IN CABANA BEDROOM NO COMPLYING- PLEASE
 PROVIDE COMPLYING WINDOW SIZE AND ADJUST ELEVATIONS,
 DESIGN PRESSURE, AND WINDOW SCHEDULE ACCORDINGLY.
  PROVIDE NOA FOR NEW EXTERIOR DOORS 1,2,3 AND DESIGN
 PRESSURES
  
 SHEET A-4
  
 TYP. WALL SECTION A
 DRAW EXACT AS BUILT CONDITION TO SCALE AND CALL OUT
 NOTE THAT ARE COORDINATED WITH DESIGN ELEMENTS.
  FASCIA AND RAFTER DIMENSIONS DO NOT MATCH- TYPO OR
 GRAPHIC ERROR PLEASE RECTIFY.
  IS THE FLAT ROOF VENTED? CLARIFY SECTION
  IS THE AS BUILT SLAB SIT ON 6MM POLYETHYLENE SHEET?
 PLEASE CONFIRM CURRENT AS BUILT CONDITIONS AND ADD NOTE
 ACCORDINGLY
  
 FBC 107.2.1 PLEASE CLARIFY
  
 COVERED ENCLOSED FRONT PORCH UNDER AC, CABANA AREA
 UNDER AC
  PROVIDE MECHANICAL DRAWINGS
  SUPPORTING DOCUMENT: ENERGY CALCULATION MUST BE SIGNED
 BY OWNER.
  
 CLEARLY EXPRESS EXACT AS BUILT CONDITIONS ON ALL
 SHEETS.
 IF ADJUSTMENT ARE REQUIRED TO MEET 2020 RESIDENTIAL FBC
 PLEASE ITEMZED.
  
  
 END OF BUILDING COMMENTS
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  