Plan Review Notes
Plan Review Notes For Permit 23031282
Permit Number 23031282
Review Stop M
Sequence Number 1
Notes
Date Text
2023-03-24 15:00:131ST REVIEW FMC
 PERMIT: 23031282
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET D-101 AND D-102 ARE MISSING FROM THIS
 SUBMITTAL. SHEET M-01 INDICATES THAT AHU-1 AND AHU-2
 ARE NEW. ARE THESE NEW SYSTEMS AS IN THERE WERE NO
 MECHANICAL SYSTEMS IN THESE AREAS BEFORE OR NEW AS IN
 REPLACEMENT UNITS? IF THEY ARE REPLACEMENT UNITS ARE
 THEY LIKE FOR LIKE REPLACEMENTS? IF SO, PLEASE PROVIDE
 THE LIKE FOR LIKE CHANGE OUT FORMS FOR EACH UNIT. FEC
 R403.7
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  