Plan Review Notes For Permit 23031241 |
Permit Number |
23031241 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-04-13 16:30:08 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. | | NEC 22O | | 2. PROVIDE PANEL SCHEDULES (W/RATING AND PROTECTION) TO | | BE IN ACCORDANCE WITH NEC 408.4(A) | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|