Plan Review Notes For Permit 23031203 |
Permit Number |
23031203 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-05-25 13:02:08 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-9.4 SHOWS A UL X630 TO BE USED FOR THE | | COLUMNS - PLEASE PROVIDE THIS UL FIRE RESISTANT | | ASSEMBLY SHOWING THE REQUIRED PAINT THICKNESS FOR THE | | FIRE RATINGS FBC WPB 107.2.1.2 | | | | 2) THE DRAWINGS PROVIDED SHOWING THE MIL THICKNESS | | NEEDS TO SHOW THE PAINT THICKNESS IN INCHES AS PER THE | | UL X630 | | | | 3) DRAWING A-1.2.0 - SHOWS THE COLUMNS TO HAVE A 2 HR | | FIRE RATING - THE DRAWINGS SHOWING THE MILS THICKNESS | | WILL NEED TO SHOW THE THICKNESS IN INCHES AND MEET A 2 | | HR FIRE RATING. | | | | 4) PRODUCT DATA SHEET PROVIDED FOR "CONTEGO" IS NOT THE | | PRODUCT IN THE UL X630 |
|