Plan Review Notes For Permit 23031203 |
Permit Number |
23031203 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-04-07 09:12:16 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | THIS IS NOT REQUIRED FOR PLAN REVIEW THIS IS A FIELD | | INSPECTION ITEM. | | | | FOR A PLAN REVIEW THE FOLLOWING ITEMS ARE REQUIRED. | | | | 1) PROVIDE A SIGNED AND SEALED DRAWING FROM THE | | ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH | | COLUMN AND THE INTUMESCENT PAINT THICKNESS. | | | | 2) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS. | | | | 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER - FBC WPB | | 107.2.1 |
|