Plan Review Notes For Permit 23031203 |
Permit Number |
23031203 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-21 12:00:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE SHOP DRAWINGS WITH A | | CHECK MARK "MAKE CORRECTIOND NOTED", HOWEVER, IT IS | | UNCLEAR IF THE SUBMITTED PLANS HAVE THOSE CORRECTIONS. | | | | FOR THE OFFICIAL RECORD, PLEASE INDICATE THAT THOSE | | CORRECTIONS HAVE BEEN INCORPORATED OR SUBMIT PLANS | | SHOWING THOSE CORREECTIONS IN A CLOUD CALLOUT. | | | | | | 2) THE SHOP DRAWINGS INDICATE AN ADDRESS OF 840 N | | DIXIE; HOWEVER, THE PERMIT APPLICATION ADDRESS | | INDICATES 740 N DIXIE. | | | | FOR THE OFFICIAL RECORD, PLEASE INDICATE WHICH ADDRESS | | IS CORRECT AND MAKE APPLICABLE CHANGES. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|