Plan Review Notes
Plan Review Notes For Permit 23031009
Permit Number 23031009
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-04-12 14:16:38PROVISO:
  
 (1) THE GATES INDICATED ARE REQUIRED TO BE 20' FOR FIRE
 DEPARTMENT ACCESS IN THE EVENT OF EMERGENCY WIDTH OF
 NOT LESS THAN 20 FT. 7.5.5.1 EVERY BUILDING SHALL BE
 ACCESSIBLE BY FIRE DEPARTMENT
 APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER
 DRIVING SURFACE OF NOT LESS THAN 6.1 M (20 FT) OF
 UNOBSTRUCTED WIDTH, HAVING THE ABILITY TO WITHSTAND THE
 LIVE LOADS OF FIRE APPARATUS, AND
 HAVING A MINIMUM OF 4.1 M (13 FT 6 IN.) OF VERTICAL
 CLEARANCE.7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT
 APPARATUS SHALL BE
 PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE
 PROJECT AND MAINTAINED UNTIL COMPLETION.
 (2)THE KNOX PADLOCK CAN BE USED IN COMBINATION WITH
 YOUR PADLOCK FOR ACCESS AND SECURITY WHEN THE INCIDENT
 IS COMPLETE.WEST PALM BEACH FIRE RESCUE KNOX PADLOCKS
 CAN BE PURCHASED AT HTTPS://WWW.KNOXBOX.COM/
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  
  
  
  
  
  
  
  