2023-04-13 11:16:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF COVERING OVER EXISTING FIRE
 LINE THAT WILL ALLOW A VEHICLE TO PASS OVER.
  
 PER NFPA 24
  
 10.4.4 PIPE UNDER DRIVEWAYS SHALL BE BURIED AT A
 MINIMUM
 DEPTH OF 3 FT (0.9 M).
  
 THERE IS NO INDICATION OF HOW DEEP THE PIPE IS.
  
 PLEASE INDICATE DIMENSIONS IN COMPLIANCE WITH THE CODE
 OR CORRECT.
  
  
  
 2) THERE ARE INDICATIONS OF THE LOCATION OF THE
 DUMPSTER IN CLOSE PROXIMITY OF THE DDCV WHERE IS MAY
 BECOME DAMAGED FROM OPENING THE GATE OR BY A VEHILCE IN
 THE PROCESS OF TRASH COLLECTION.
  
 PER NFPA 24
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
  
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 PLEASE PROVIDE BOLLARDS OF SIMILARE PROTECTION
 EQUIPMENT.
  
  
  
 3 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  