Plan Review Notes For Permit 23030984 |
Permit Number |
23030984 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-04-13 11:16:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF COVERING OVER EXISTING FIRE | | LINE THAT WILL ALLOW A VEHICLE TO PASS OVER. | | | | PER NFPA 24 | | | | 10.4.4 PIPE UNDER DRIVEWAYS SHALL BE BURIED AT A | | MINIMUM | | DEPTH OF 3 FT (0.9 M). | | | | THERE IS NO INDICATION OF HOW DEEP THE PIPE IS. | | | | PLEASE INDICATE DIMENSIONS IN COMPLIANCE WITH THE CODE | | OR CORRECT. | | | | | | | | 2) THERE ARE INDICATIONS OF THE LOCATION OF THE | | DUMPSTER IN CLOSE PROXIMITY OF THE DDCV WHERE IS MAY | | BECOME DAMAGED FROM OPENING THE GATE OR BY A VEHILCE IN | | THE PROCESS OF TRASH COLLECTION. | | | | PER NFPA 24 | | | | 6.5 BACKFLOW PREVENTION ASSEMBLIES. | | | | 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED, | | THEY | | SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE | | NEEDED. | | | | PLEASE PROVIDE BOLLARDS OF SIMILARE PROTECTION | | EQUIPMENT. | | | | | | | | 3 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|