Date |
Text |
2023-03-16 13:40:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE |
| LOCATION OF THE PROPOSED FLOORING INSTALLATION. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOOR PLAN |
| INDICATING THE LOCATION OF THE PROPOSED FLOORING |
| INSTALLATION. |
| |
| |
| |
| 2) THE SUBMITTED SPECIFICATION SHEET WITH MOHAWK HOME |
| RIGID VINYL ON IT APPEARS TO BE FOR THE SOUND |
| TRANSMISSION AND DOES NOT INDICATE ANY FIRE RESISTIVE |
| RATING. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE CONFIRM THE VINYL |
| FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| THE FIRE BEHAVIOR RATING. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |