2023-03-14 16:16:49 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT A DIMENSIONED DIAGRAM DRAWING OF THE ROOF. |
| SHOW WHICH PARTS OF THE ROOF ARE WOOD AND WHICH ARE |
| CONCRETE. PROVIDE THE AREAS OF EACH TYPE OF ROOF. SHOW |
| THE LOCATIONS AND SIZES OF ALL EXISTING ROOF DRAINS AND |
| SCUPPERS. SPECIFY THE LOCATION AND HEIGHTS OF ANY |
| PARAPET WALLS. FBC 107.2.1 |
| |
| 2) PROVIDE FLASHING DETAILS OF THE PRAPET WALLS. FBC |
| 1503 |
| |
| 3) SHOW THE SLOPES OF THE ROOFS ON THE DRAWINGS. FBC |
| 1503 |
| |
| 4) THE W-30 ROOF SYSTEM ON PAGE 10 OF FL2533-R28 HAS A |
| MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS IS NOT |
| ADEQUATE FOR A FLAT ROOF IN A LOCATION THAT HAS A 170 |
| MPH VULT WIND SPEED AND EXPOSURE CATEGORY C. SUBMIT |
| SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS FOR |
| MECHANICALLY FASTENED SYSTEMS THAT ALLOW THEM. SEE |
| LIMITATION NUMBER 9 ON PAGE 3. FBC 107.2.1 |
| |
| 5) THE VALUE OF $6,004.00 APPEARS THAT IT MIGHT BE LOW |
| DEPENDING ON THE AREA OF ROOF THAT IS BEING REPLACED. |
| PROVIDE A COMPLETE SCOPE OF WORK. BUILDING PERMIT |
| VALUATION. FOR PERMITTING PURPOSES, VALUATION OF FBC |
| 109.3 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |