Plan Review Notes
Plan Review Notes For Permit 23030877
Permit Number 23030877
Review Stop M
Sequence Number 1
Notes
Date Text
2023-03-16 10:37:181ST REVIEW FMC
 PERMIT: 23030877
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS NEW APPLICATION STATES IT IS, IN PART, FOR
 MECHANICAL DUCTWORK WAS REPLACED AND LOCATION OF AIR
 HANDLER. THERE IS ONLY 1 AHU SHOWN ON THE DRAWING BUT
 THE OUTDOOR AIR CALCULATIONS ARE LABELED SYSTEM 1 AND
 2. WHERE IS THE SECOND SYSTEM LOCATED? WAS THE DUCTWORK
 CHANGED FOR THIS UNIT AS WELL? IF SO PLEASE SHOW THIS
 ON THE DRAWING. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  