Plan Review Notes For Permit 23030722 |
Permit Number |
23030722 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-04-03 07:14:34 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 23030722 | | 4/3/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST | | REVIEW COPIED BELOW WAS NOT ADDRESSED. THE DEVICE SHALL | | BE LEAD-FREE. | | | | 1) AN RPZ (REDUCED PRESSURE PRINCIPLE ASSEMBLY) IS | | REQUIRED FOR THE POTABLE WATER SERVICE HOWEVER A SPEC | | SHEET FOR A DOUBLE CHECK BACKFLOW HAS BEEN SUBMITTED. | | PLEASE NOTE POTABLE WATER SERVICE BF PREVENTERS SHALL | | MEET THE REQUIREMENTS OF NSF/ANSI/CAN 61 (0.25% MAX | | WEIGHTED AVERAGE LEAD CONTENT). SUBMIT A SPEC SHEET FOR | | A DEVICE THAT MEETS COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|