Plan Review Notes For Permit 23030657 |
Permit Number |
23030657 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-04-21 09:51:28 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC P2705.1 #5 -- ACCORDING TO THE SCALE, IT | | APPEARS THAT YOUR SHOWER IS ALMOST 36". WITH THE | | DIMENSIONS OF THE BATHROOM, IT APPEARS YOU MAY NOT HAVE | | THE MINIMUM 30" FOR THE LAV AND 30" FOR THE WATER | | CLOSET. PLEASE SHOW THE FIXTURE SPACING TO MEET THIS | | CODE SECTION. | | | | 2. 2020 FRC P3108.2.1 - THE WATER CLOSET AND SHOWER ARE | | BOTH UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE | | HORIZONTALLY WET VENTED BRANCH. ONLY ONE FIXTURE IS | | ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S | | CONNECTION. PLEASE RECONFIGURE. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | |
|