2023-04-21 09:51:281ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P2705.1 #5 -- ACCORDING TO THE SCALE, IT
 APPEARS THAT YOUR SHOWER IS ALMOST 36". WITH THE
 DIMENSIONS OF THE BATHROOM, IT APPEARS YOU MAY NOT HAVE
 THE MINIMUM 30" FOR THE LAV AND 30" FOR THE WATER
 CLOSET. PLEASE SHOW THE FIXTURE SPACING TO MEET THIS
 CODE SECTION.
  
 2. 2020 FRC P3108.2.1 - THE WATER CLOSET AND SHOWER ARE
 BOTH UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE
 HORIZONTALLY WET VENTED BRANCH. ONLY ONE FIXTURE IS
 ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S
 CONNECTION. PLEASE RECONFIGURE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  