Plan Review Notes
Plan Review Notes For Permit 23030594
Permit Number 23030594
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-16 10:18:16FIRE PROVISO COMMENTS:
  
 (1) WITH THE REMOVAL AND ADDITION OF WALLS, PROPERLY
 LICENSED CONTRACTORS SHALL REVIEW TO ENSURE CODE
 COMPLIANT LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) ARE MAINTAINED.
  
 (2) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE INCLUDING PAINTING, DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
  
 C. WALKER
  