Plan Review Notes For Permit 23030553 |
Permit Number |
23030553 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-24 16:02:24 | EV CHARGING STATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE THE CHARGING POST FOUNDATION AND | | ATTACHMENT TO FOUNDATION DETAILS TO MEET THE REQUIRED | | WIND DESIGN PRESSURES. FBC 1609 | | | | 2) THE LOCATION OF THE EV CHARGERS IS NOT CLEAR - ARE | | THEY FOR THE GENERAL PUBLIC OR THE SERVICE FACILITY | | ONLY. | | | | 3) EV CHARGERS FOR THE GENERAL PUBLIC - PLEASE SHOW | | THAT AT LEAST 1 OF THE CHARGING STATIONS IS AN | | ACCESSIBLE PARKING SPACE, ACCESS AISLE, SIGNAGE ETC. | | PER FBC 502 | | FBC 406.1.7 ELECTRIC VEHICLE CHARGING STATIONS. | | ACCESSIBILITY TO ELECTRIC VEHICLE CHARGING STATIONS | | SHALL BE PROVIDED IN ACCORDANCE WITH CHAPTER 11. | | | | 4) DRAWINGS PROVIDED NEED TO BE SIGNED AND SEALED BY | | THE DESIGNER. |
|