2023-04-10 08:55:08 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT-23030516 |
| 4/10/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. IMPORTANT NOTE. THE |
| FOLLOWING REVIEW IS FOR PLUMBING ONLY. A SEPARATE |
| TENANT BUILD-OUT PERMIT FOR THE COMMERCIAL KITCHEN |
| AND/OR NEW RESTAURANT IS REQUIRED. |
| |
| 1) THE NEW PLUMBING DRAWINGS ARE NOT IN COMPLIANCE WITH |
| THE FOLLOWING FPC-2020 CODE SECTIONS. |
| |
| A) SEC. 910.1 & 1003.3.5: AS NOTED IN THE 1ST REVIEW, A |
| TRAP AND VENT ARE REQUIRED FOR THE 3-COMPARTMENT SINK. |
| MANUFACTURER???S INSTALL GUIDELINES FOR THE SCHIER GB-1 |
| SHOW SINK TRAP AND VENT UPSTREAM OF THE INTERCEPTOR. |
| B) SEC. 918.8: AN AAV SHALL NOT BE USED TO VENT THE |
| GREASE TRAP. |
| C) SEC. 904.1: THE BUILDING DRAIN REQUIRES NOT LESS |
| THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. |
| D) SEC. 608.3: A BACKFLOW PREVENTER IS REQUIRED FOR THE |
| WATER SUPPLY LINE TO THE ICE MAKER. |
| E) SEC. 801.2: AN INDIRECT WASTE RECEPTOR IS REQUIRED |
| TO RECEIVE THE DRAINAGE FROM THE ICE MAKER. |
| |
| 2) PLEASE NOTE OTHER LICENSING AGENCIES SUCH AS THE PB |
| DEPARTMENT OF HEALTH, DBPR FOOD AND BEVERAGE LICENSING |
| DEPT. OR DEPT. OF AGRICULTURE MAY REQUIRE A FLOOR DRAIN |
| IN THE KITCHEN FOR SANITARY PURPOSES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |