Plan Review Notes
Plan Review Notes For Permit 23030516
Permit Number 23030516
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-10 08:55:082ND REVIEW FBC-2020 PLUMBING
 PERMIT-23030516
 4/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. IMPORTANT NOTE. THE
 FOLLOWING REVIEW IS FOR PLUMBING ONLY. A SEPARATE
 TENANT BUILD-OUT PERMIT FOR THE COMMERCIAL KITCHEN
 AND/OR NEW RESTAURANT IS REQUIRED.
  
 1) THE NEW PLUMBING DRAWINGS ARE NOT IN COMPLIANCE WITH
 THE FOLLOWING FPC-2020 CODE SECTIONS.
  
 A) SEC. 910.1 & 1003.3.5: AS NOTED IN THE 1ST REVIEW, A
 TRAP AND VENT ARE REQUIRED FOR THE 3-COMPARTMENT SINK.
 MANUFACTURER???S INSTALL GUIDELINES FOR THE SCHIER GB-1
 SHOW SINK TRAP AND VENT UPSTREAM OF THE INTERCEPTOR.
 B) SEC. 918.8: AN AAV SHALL NOT BE USED TO VENT THE
 GREASE TRAP.
 C) SEC. 904.1: THE BUILDING DRAIN REQUIRES NOT LESS
 THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS.
 D) SEC. 608.3: A BACKFLOW PREVENTER IS REQUIRED FOR THE
 WATER SUPPLY LINE TO THE ICE MAKER.
 E) SEC. 801.2: AN INDIRECT WASTE RECEPTOR IS REQUIRED
 TO RECEIVE THE DRAINAGE FROM THE ICE MAKER.
  
 2) PLEASE NOTE OTHER LICENSING AGENCIES SUCH AS THE PB
 DEPARTMENT OF HEALTH, DBPR FOOD AND BEVERAGE LICENSING
 DEPT. OR DEPT. OF AGRICULTURE MAY REQUIRE A FLOOR DRAIN
 IN THE KITCHEN FOR SANITARY PURPOSES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  