Plan Review Notes For Permit 23030515 |
Permit Number |
23030515 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-04-10 09:08:43 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT-23030515 | | 4/10/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE NEW PLUMBING DRAWINGS ARE NOT IN COMPLIANCE WITH | | THE FOLLOWING FPC-2020 CODE SECTIONS. | | | | A) SEC. 910.1 & 1003.3.5: AS NOTED IN THE 1ST REVIEW, A | | TRAP AND VENT ARE REQUIRED FOR THE 3-COMPARTMENT SINK. | | MANUFACTURER'S INSTALL GUIDELINES FOR THE SCHIER GB-1 | | SHOW SINK TRAP AND VENT UPSTREAM OF THE INTERCEPTOR. | | B) SEC. 1003.3.5: THE REQUESTED GREASE IONTERCEPTOR | | SIZING CALCULATIONS WERE NOT PROVIDED. | | C) SEC. 918.8: AN AAV SHALL NOT BE USED TO VENT THE | | GREASE TRAP. | | D) SEC. 904.1: THE BUILDING DRAIN REQUIRES NOT LESS | | THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|