Plan Review Notes
Plan Review Notes For Permit 23030515
Permit Number 23030515
Review Stop P
Sequence Number 1
Notes
Date Text
2023-03-13 12:23:061ST REVIEW FBC-2020 PLUMBING
 PERMIT-23030515
 3/9/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A MANUFACTURER'S SPECIFICATION SHEET FOR THE
 IRONWALLS INTERCEPTOR THAT INDICATES THE UNIT MEETS
 EITHER THE ASME AND/OR PDI DESIGN AND TESTING STANDARD
 FOR HYDROMECHANICAL GREASE INTERCEPTORS AS REQUIRED BY
 SEC. 1003.3.5; OR THE IAPMO/ANSI Z1001 STANDARD FOR
 GRAVITY GREASE INTERCEPTORS AS REQUIRED BY SEC.
 1003.3.7 FBC P. I WAS UNABLE TO LOCATE TESTING STANDARD
 INFORMATION ONLINE FOR THE UNIT.
  
 2) PROVIDE GREASE WASTE SIZING CALCULATIONS IN
 ACCORDANCE WITH SECS.1003.3.5 FBC P FOR HYDROMECHANICAL
 TYPES OR 1003.3.7 FOR GRAVITY TYPES.
  
 3) ISOMETRIC DRAWING: PLEASE CORRECT THE DRAWINGS PER
 ITEMS A, B, & C BELOW. PLEASE NOTE THAT INSTALLATION OF
 THE INTERCEPTOR AND ASSOCIATED PLUMBING PIPING SHALL BE
 IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION
 GUIDELINES WHICH SHALL BE ONSITE FOR INSPECTION- SECS.
 1003.3.5 & 1003.3.7 FBC P.
  
 A) THE INTERCEPTOR DISCHARGE PIPE SHALL BE DIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE PIPE, NOT INDIRECTLY
 AS THE DRAWING SHOWS- SEC. 1003.3.8 FBC P.
  
 B) BASED ON OTHER MANUFACTURER'S INSTALLATION
 GUIDELINES THE TYPICAL INSTALLATION FOR AN INTERCEPTOR
 MOUNTED ON THE FLOOR, INSTEAD OF UNDER THE FLOOR, IS TO
 PROVIDE A TRAP AND VENT PIPE FOR THE 3-COMPARTMENT SINK
 AND DIRECT PIPE CONNECTIONS IN AND OUT OF THE UNIT.
 SOME MANUFACTURER'S REQUIRE A FLOW CONTROL AIR INTAKE
 PIPE AND A VENT FOR THE DISCHARGE PIPE. PLEASE CONSULT
 THE MANUFACTURER'S GUIDELINES. IF THE INTERCEPTOR IS
 INSTALLED UNDER THE FLOOR TYPICALLY AN INDIRECT WASTE
 RECEPTOR WITH TRAP AND VENT SHALL BE PROVIDED FOR THE
 3-COMPARTMENT WITH DIRECT FIXTURE DRAIN AND DISCHARGE
 PIPE CONNECTIONS. AS NOTE ABOVE MANUFACTURER'S
 GUIDELINES WILL ALSO APPLY.
  
 C) PROVIDE AN INDIVIDUAL AAV FOR THE HANDSINK FIXTURE
 DRAIN- TABLE 909.1 & SEC. 918.3 FBC P.
  
 4) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 SHALL BE ON THE DRAWINGS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER