2023-03-13 12:23:06 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-23030515 |
| 3/9/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT A MANUFACTURER'S SPECIFICATION SHEET FOR THE |
| IRONWALLS INTERCEPTOR THAT INDICATES THE UNIT MEETS |
| EITHER THE ASME AND/OR PDI DESIGN AND TESTING STANDARD |
| FOR HYDROMECHANICAL GREASE INTERCEPTORS AS REQUIRED BY |
| SEC. 1003.3.5; OR THE IAPMO/ANSI Z1001 STANDARD FOR |
| GRAVITY GREASE INTERCEPTORS AS REQUIRED BY SEC. |
| 1003.3.7 FBC P. I WAS UNABLE TO LOCATE TESTING STANDARD |
| INFORMATION ONLINE FOR THE UNIT. |
| |
| 2) PROVIDE GREASE WASTE SIZING CALCULATIONS IN |
| ACCORDANCE WITH SECS.1003.3.5 FBC P FOR HYDROMECHANICAL |
| TYPES OR 1003.3.7 FOR GRAVITY TYPES. |
| |
| 3) ISOMETRIC DRAWING: PLEASE CORRECT THE DRAWINGS PER |
| ITEMS A, B, & C BELOW. PLEASE NOTE THAT INSTALLATION OF |
| THE INTERCEPTOR AND ASSOCIATED PLUMBING PIPING SHALL BE |
| IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION |
| GUIDELINES WHICH SHALL BE ONSITE FOR INSPECTION- SECS. |
| 1003.3.5 & 1003.3.7 FBC P. |
| |
| A) THE INTERCEPTOR DISCHARGE PIPE SHALL BE DIRECTLY |
| CONNECTED TO THE SANITARY DRAINAGE PIPE, NOT INDIRECTLY |
| AS THE DRAWING SHOWS- SEC. 1003.3.8 FBC P. |
| |
| B) BASED ON OTHER MANUFACTURER'S INSTALLATION |
| GUIDELINES THE TYPICAL INSTALLATION FOR AN INTERCEPTOR |
| MOUNTED ON THE FLOOR, INSTEAD OF UNDER THE FLOOR, IS TO |
| PROVIDE A TRAP AND VENT PIPE FOR THE 3-COMPARTMENT SINK |
| AND DIRECT PIPE CONNECTIONS IN AND OUT OF THE UNIT. |
| SOME MANUFACTURER'S REQUIRE A FLOW CONTROL AIR INTAKE |
| PIPE AND A VENT FOR THE DISCHARGE PIPE. PLEASE CONSULT |
| THE MANUFACTURER'S GUIDELINES. IF THE INTERCEPTOR IS |
| INSTALLED UNDER THE FLOOR TYPICALLY AN INDIRECT WASTE |
| RECEPTOR WITH TRAP AND VENT SHALL BE PROVIDED FOR THE |
| 3-COMPARTMENT WITH DIRECT FIXTURE DRAIN AND DISCHARGE |
| PIPE CONNECTIONS. AS NOTE ABOVE MANUFACTURER'S |
| GUIDELINES WILL ALSO APPLY. |
| |
| C) PROVIDE AN INDIVIDUAL AAV FOR THE HANDSINK FIXTURE |
| DRAIN- TABLE 909.1 & SEC. 918.3 FBC P. |
| |
| 4) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR |
| SHALL BE ON THE DRAWINGS- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |