Plan Review Notes
Plan Review Notes For Permit 23030509
Permit Number 23030509
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2023-03-22 13:26:151. VOLUNTARY ENGINEERED DESIGN PRESSURES SUBMITTED MUST
 BE BASED ON CORRECT DESIGN CRITERIA. PLEASE VERIFY THE
 FOLLOWING DESIGN CRITERIA: (A) STRUCTURE IS LISTED AS
 PARTIALLY ENCLOSED. (B) TRIBUTARY AREA CALCULATIONS FOR
 OPENINGS 1 AND 2 ARE NOT CORRECT. FBC 107.2 2. PLEASE
 PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE PLAN,
 DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC B
 1405.4.