2023-04-26 15:12:24 | ELECTRIC REVIEW FAILED |
| |
| 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM INCLUDING |
| ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND |
| OVERCURRENT PROTECTION SIZES. NEC 215.5 |
| |
| 215.5 DIAGRAMS OF FEEDERS. |
| IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A |
| DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR |
| TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM |
| SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR |
| OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL |
| CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE |
| DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING |
| DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO |
| BE USED. |
| |
| 2) PLEASE PROVIDE A SITE PLAN LOCATING ALL ELECTRICAL |
| EQUIPMENT. FBC 107.2 |
| |
| FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |