2023-03-09 11:38:22 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-23030381 |
| 3/9/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P100- IMPORTANT NOTE: SEPARATE PERMITS ARE |
| REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW |
| PREVENTER AND THE GREASE INTERCEPTOR, AND PERMIT |
| APPLICATIONS FOR EACH SHALL BE SUBMITTED PRIOR TO |
| APPROVAL OF THE MAIN PLUMBING PLANS FOR THE PROJECT. |
| YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF |
| YOU DO NOT HAVE CONTRACTORS SELECTED BY EMAILING |
| COMPLETED PERMIT APPLICATIONS TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2) P-100 & P-200: PROVIDE PLUMBING FIXTURE CALCULATIONS |
| FOR THE NEW BUILDING IN ACCORDANCE WITH TABLE 403.1 FBC |
| P. PROVIDE SCHEDULES THAT SHOW THE REQUIRED AND |
| PROVIDED NUMBER OF FIXTURES FOR EACH SEPARATE OCCUPANCY |
| OR TENANT SPACE. THE CALCULATIONS SHALL CLARIFY WHICH |
| TENANT SPACES WILL ARE BEING SERVICED BY THE NEW GANG |
| BATHROOMS, DRINKING FOUNTAINS AND JANITOR???S SINK. |
| |
| 3) P-100: SANITARY AND GREASE WASTE STUB UPS ARE NOT |
| SHOWN IN THE FUTURE TENANT 110 SPACE. IT WOULD APPEAR |
| AT MINIMUM A SANITARY STUB-UP WOULD BE NECESSARY- SEC. |
| 107.2.1 WPB. |
| |
| 4) P-100: NUMEROUS PLUMBING KEY NOTES REFERENCE THE |
| CIVIL PLANS WHICH HAVE NOT BEEN UPLOADED FOR REVIEW- |
| SEC. 107.2.1 WPB. |
| |
| 5) P-100: THE FUTURE GREASE INTERCEPTOR PLAN REVIEW |
| SUBMITTAL SHALL INCLUDE THE FOLLOWING ITEMS. |
| |
| A) GREASE WASTE PIPING ISOMETRIC AND A PIPING LAYOUT |
| PLAN SHOWING PIPE RUNS FROM THE INDIVIDUAL FIXTURES TO |
| THE MAIN WASTE LINE, WASTE LINE RUN TO THE INTERCEPTOR, |
| AND OUTLET LINE TO POINT OF CONNECTION TO THE SANITARY |
| SEWER- SEC. 107.2.1 WPB. |
| |
| B) EQUIPMENT SCHEDULE INDICATING THE MAKE, AND MODEL |
| AND CAPACITY OF THE UNIT- SEC. 1003.3.5. |
| |
| C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| OR PDI G101 FOR HYDROMECHANICAL TYPES- SEC.1003.5.1. |
| |
| D) AN ENLARGED PIPING DIAGRAM OR ISOMETRIC SHOWING THE |
| SIZES OF INLETS, OUTLETS, CLEANOUTS, AND VENTS- SEC. |
| 107.3.5.1.3 WPB. PLEASE INCLUDE A DETAIL FOR THE |
| CLEANOUT WHICH WILL BE USED AS THE SAMPLING PORT BY THE |
| WPB UTILITIES DEPT. |
| |
| 6) P-700: THE SANITARY RISER APPEARS TO SHOW IMPROPER |
| WET-VENTING FOR THE MEN???S AND WOMEN???S BATHROOM |
| FIXTURES PER ITEMS A-D BELOW. |
| |
| A) URINALS ARE NOT INCLUDED IN THE DEFINITION OF A |
| BATHROOM GROUP SO THEIR FIXTURE DRAINS SHALL NOT |
| CONNECT TO THE WET VENT, AND THEIR DRY VENTS SHALL NOT |
| BE THE DRY VENT FOR THE SYSTEM- SECS. 202 & 912.1 FBC |
| P. IN ORDER TO FIX THE BRANCH, THE URINAL DRAINS SHALL |
| CONNECT DOWNSTREAM OF THE L2/WC-1 WET VENT, AND A |
| COMMON VENT OR INDIVIDUAL VENTS FOR THE URINALS SHALL |
| BE PROVIDED- SECS. 910.1 & 911.1. |
| |
| B) THE TWO WET VENT BRANCHES SHOWING 3- WATER CLOSETS |
| (WC-1) AND 3- LAVATORIES (L-1) ARE NOT IN COMPLIANCE |
| WITH 912.1 BECAUSE NOT MORE THAN TWO OF ANY FIXTURE |
| TYPE CAN CONNECT TO A WET-VENT SYSTEM. TO FIX THE |
| BRANCHES, INDIVIDUAL OR COMMON WC-1 & L-1 VENTS SHALL |
| BE PROVIDED- SECS. 910.1 & 911. THE L-1 BRANCH CAN ALSO |
| BE CIRCUIT VENTED IF DESIGNED IN ACCORDANCE WITH SEC. |
| 914.1- 914.3. |
| |
| C) THE BRANCH SHOWING THE 3- LAVATORIES AND THE |
| JANITOR'S SINK WITH INDIVIDUAL VENT CAN BE FIXED BY |
| PROVIDING EITHER INDIVIDUAL VENTS OR COMMON VENTS FOR |
| THE LAVS, OR A CIRCUIT VENT FOR THE WHOLE BRANCH CAN BE |
| DESIGNED IN ACCORDANCE WITH SECS. 914.1- 914.3 FBC P. |
| |
| D) PROVIDE VENTING FOR THE HD AND FD-1- SEC. 901.2.1 |
| FBC P. PLEASE NOTE THAT BASED ON P-100 THERE APPEARS TO |
| BE ONE FD-1 MISSING FROM THE ISOMETRIC DRAWING. |
| |
| 7) P-700: SHOW TRAP SEAL PROTECTION FOR THE FD-1 AND |
| HD-1: SEC. 1002.4.1 FBC P. |
| |
| 8) P-700 WATER RISER: SHOW THE SIZES OF THE SUPPLY |
| PIPES TO UR-1 AND WC-1- TABLE 604.5 FBC P. |
| |
| 9) P-700: TEMPERED WATER SHALL BE DELIVERED FROM THE |
| LAVATORIES THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| THAT CONFORMS TO ASSE 1070- SECS. 419.5 & 607.1.2 FBC |
| P. |
| |
| 10) P-700: THE 3/4 -INCH HOT WATER FIXTURE SUPPLY PIPES |
| TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE |
| LENGTHS OF 0.5 FT. FROM THE HOT WATER SOURCE TO THE |
| PIPE TERMINATION. THE NEAREST SOURCE IN THIS CASE IS |
| THE RECIRCULATION LINE- TABLE C404.5.1 FBC ENERGY. |
| |
| 11) P-500: PLEASE PROVIDE A WATER HEATER DETAIL THAT |
| SHOW THE PIPING CONNECTIONS TO THE RECIRCULATION PUMP, |
| REQUIRED EXPANSION TANK AND THE REQUIRED MASTER |
| THERMOSTATIC MIXING VALVE- SECS. 607.2.2 & 607.3 FBC P. |
| PLEASE NOTE THE MASTER MIXING VALVE IS REQUIRED BECAUSE |
| THE THERMOSTAT ON THE WATER HEATER CANNOT BE THE |
| TEMPERATURE LIMITING MEANS FOR THE HOT WATER SYSTEM- |
| SEC. 607.1.1. |
| |
| 12) P-700: PLEASE SHOW THE DRAINAGE GPM'S AT THE ROOF |
| DRAINS AND THE ACCUMULATIVE GPM FLOW THROUGH THE |
| VERTICAL LEADERS AND HORIZONAL STORM PIPES TO THE |
| DISPOSAL LOCATIONS- TABLES 1106.2 & 1106.3 FBC P. |
| |
| 13) A104 & A104A: PLEASE PROVIDE THE FOLLOWING FBC ACC |
| COMPLIANCE DETAILS FOR THE ACCESSIBLE BATHROOM FIXTURES |
| AND DRINKING FOUNTAINS. PLEASE NOTE KEYNOTES 1-4 NOT |
| SHOWN ON THE DRAWINGS. |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- SEC. 606.2. |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| AND PARTITIONS- SEC. 604.2. |
| E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- SEC. 604.4. |
| F) HEIGHTS OF THE ACCESSIBLE COMPARTMENT LAVATORY SINK |
| RIMS FROM THE FINISHED FLOORS- SEC. 606.3. |
| G) HEIGHTS OF THE ACCESSIBLE COMPARTMENT MIRRORS FROM |
| THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION |
| 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| FIGURES 604.5.1 604.5.2. |
| I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| 604.7. |
| J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| 606.2. |
| K) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| TO THE FOUNTAIN- SEC. 602.2 FBC ACC, AND SHOW HOW THE |
| LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| SEC. 307.2 PROTRUSION LIMITS. IT APPEARS ONE SIDE OF |
| THE FOUNTAIN IS BEYOND THE 4-INCH MAXIMUM PROTRUSION |
| LIMITATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |