Plan Review Notes For Permit 23030381
Permit Number 23030381
Review Stop P
Sequence Number 1
Notes
Date Text
2023-03-09 11:38:221ST REVIEW FBC-2020 PLUMBING
 PERMIT-23030381
 3/9/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P100- IMPORTANT NOTE: SEPARATE PERMITS ARE
 REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER AND THE GREASE INTERCEPTOR, AND PERMIT
 APPLICATIONS FOR EACH SHALL BE SUBMITTED PRIOR TO
 APPROVAL OF THE MAIN PLUMBING PLANS FOR THE PROJECT.
 YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE CONTRACTORS SELECTED BY EMAILING
 COMPLETED PERMIT APPLICATIONS TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2) P-100 & P-200: PROVIDE PLUMBING FIXTURE CALCULATIONS
 FOR THE NEW BUILDING IN ACCORDANCE WITH TABLE 403.1 FBC
 P. PROVIDE SCHEDULES THAT SHOW THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES FOR EACH SEPARATE OCCUPANCY
 OR TENANT SPACE. THE CALCULATIONS SHALL CLARIFY WHICH
 TENANT SPACES WILL ARE BEING SERVICED BY THE NEW GANG
 BATHROOMS, DRINKING FOUNTAINS AND JANITOR???S SINK.
  
 3) P-100: SANITARY AND GREASE WASTE STUB UPS ARE NOT
 SHOWN IN THE FUTURE TENANT 110 SPACE. IT WOULD APPEAR
 AT MINIMUM A SANITARY STUB-UP WOULD BE NECESSARY- SEC.
 107.2.1 WPB.
  
 4) P-100: NUMEROUS PLUMBING KEY NOTES REFERENCE THE
 CIVIL PLANS WHICH HAVE NOT BEEN UPLOADED FOR REVIEW-
 SEC. 107.2.1 WPB.
  
 5) P-100: THE FUTURE GREASE INTERCEPTOR PLAN REVIEW
 SUBMITTAL SHALL INCLUDE THE FOLLOWING ITEMS.
  
 A) GREASE WASTE PIPING ISOMETRIC AND A PIPING LAYOUT
 PLAN SHOWING PIPE RUNS FROM THE INDIVIDUAL FIXTURES TO
 THE MAIN WASTE LINE, WASTE LINE RUN TO THE INTERCEPTOR,
 AND OUTLET LINE TO POINT OF CONNECTION TO THE SANITARY
 SEWER- SEC. 107.2.1 WPB.
  
 B) EQUIPMENT SCHEDULE INDICATING THE MAKE, AND MODEL
 AND CAPACITY OF THE UNIT- SEC. 1003.3.5.
  
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES- SEC.1003.5.1.
  
 D) AN ENLARGED PIPING DIAGRAM OR ISOMETRIC SHOWING THE
 SIZES OF INLETS, OUTLETS, CLEANOUTS, AND VENTS- SEC.
 107.3.5.1.3 WPB. PLEASE INCLUDE A DETAIL FOR THE
 CLEANOUT WHICH WILL BE USED AS THE SAMPLING PORT BY THE
 WPB UTILITIES DEPT.
  
 6) P-700: THE SANITARY RISER APPEARS TO SHOW IMPROPER
 WET-VENTING FOR THE MEN???S AND WOMEN???S BATHROOM
 FIXTURES PER ITEMS A-D BELOW.
  
 A) URINALS ARE NOT INCLUDED IN THE DEFINITION OF A
 BATHROOM GROUP SO THEIR FIXTURE DRAINS SHALL NOT
 CONNECT TO THE WET VENT, AND THEIR DRY VENTS SHALL NOT
 BE THE DRY VENT FOR THE SYSTEM- SECS. 202 & 912.1 FBC
 P. IN ORDER TO FIX THE BRANCH, THE URINAL DRAINS SHALL
 CONNECT DOWNSTREAM OF THE L2/WC-1 WET VENT, AND A
 COMMON VENT OR INDIVIDUAL VENTS FOR THE URINALS SHALL
 BE PROVIDED- SECS. 910.1 & 911.1.
  
 B) THE TWO WET VENT BRANCHES SHOWING 3- WATER CLOSETS
 (WC-1) AND 3- LAVATORIES (L-1) ARE NOT IN COMPLIANCE
 WITH 912.1 BECAUSE NOT MORE THAN TWO OF ANY FIXTURE
 TYPE CAN CONNECT TO A WET-VENT SYSTEM. TO FIX THE
 BRANCHES, INDIVIDUAL OR COMMON WC-1 & L-1 VENTS SHALL
 BE PROVIDED- SECS. 910.1 & 911. THE L-1 BRANCH CAN ALSO
 BE CIRCUIT VENTED IF DESIGNED IN ACCORDANCE WITH SEC.
 914.1- 914.3.
  
 C) THE BRANCH SHOWING THE 3- LAVATORIES AND THE
 JANITOR'S SINK WITH INDIVIDUAL VENT CAN BE FIXED BY
 PROVIDING EITHER INDIVIDUAL VENTS OR COMMON VENTS FOR
 THE LAVS, OR A CIRCUIT VENT FOR THE WHOLE BRANCH CAN BE
 DESIGNED IN ACCORDANCE WITH SECS. 914.1- 914.3 FBC P.
  
 D) PROVIDE VENTING FOR THE HD AND FD-1- SEC. 901.2.1
 FBC P. PLEASE NOTE THAT BASED ON P-100 THERE APPEARS TO
 BE ONE FD-1 MISSING FROM THE ISOMETRIC DRAWING.
  
 7) P-700: SHOW TRAP SEAL PROTECTION FOR THE FD-1 AND
 HD-1: SEC. 1002.4.1 FBC P.
  
 8) P-700 WATER RISER: SHOW THE SIZES OF THE SUPPLY
 PIPES TO UR-1 AND WC-1- TABLE 604.5 FBC P.
  
 9) P-700: TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORIES THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SECS. 419.5 & 607.1.2 FBC
 P.
  
 10) P-700: THE 3/4 -INCH HOT WATER FIXTURE SUPPLY PIPES
 TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE
 LENGTHS OF 0.5 FT. FROM THE HOT WATER SOURCE TO THE
 PIPE TERMINATION. THE NEAREST SOURCE IN THIS CASE IS
 THE RECIRCULATION LINE- TABLE C404.5.1 FBC ENERGY.
  
 11) P-500: PLEASE PROVIDE A WATER HEATER DETAIL THAT
 SHOW THE PIPING CONNECTIONS TO THE RECIRCULATION PUMP,
 REQUIRED EXPANSION TANK AND THE REQUIRED MASTER
 THERMOSTATIC MIXING VALVE- SECS. 607.2.2 & 607.3 FBC P.
 PLEASE NOTE THE MASTER MIXING VALVE IS REQUIRED BECAUSE
 THE THERMOSTAT ON THE WATER HEATER CANNOT BE THE
 TEMPERATURE LIMITING MEANS FOR THE HOT WATER SYSTEM-
 SEC. 607.1.1.
  
 12) P-700: PLEASE SHOW THE DRAINAGE GPM'S AT THE ROOF
 DRAINS AND THE ACCUMULATIVE GPM FLOW THROUGH THE
 VERTICAL LEADERS AND HORIZONAL STORM PIPES TO THE
 DISPOSAL LOCATIONS- TABLES 1106.2 & 1106.3 FBC P.
  
 13) A104 & A104A: PLEASE PROVIDE THE FOLLOWING FBC ACC
 COMPLIANCE DETAILS FOR THE ACCESSIBLE BATHROOM FIXTURES
 AND DRINKING FOUNTAINS. PLEASE NOTE KEYNOTES 1-4 NOT
 SHOWN ON THE DRAWINGS.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 AND PARTITIONS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE ACCESSIBLE COMPARTMENT LAVATORY SINK
 RIMS FROM THE FINISHED FLOORS- SEC. 606.3.
 G) HEIGHTS OF THE ACCESSIBLE COMPARTMENT MIRRORS FROM
 THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION
 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 604.5.2.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
 K) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SEC. 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SEC. 307.2 PROTRUSION LIMITS. IT APPEARS ONE SIDE OF
 THE FOUNTAIN IS BEYOND THE 4-INCH MAXIMUM PROTRUSION
 LIMITATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER