2023-03-23 14:48:28 | NEW COMMERCIAL BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW THE BUILDING SET BACKS FROM THE PROPERTY |
| LINES - FBC WPB 107.2.5 |
| |
| 2) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE |
| BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE |
| SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC |
| WPB 107.2.5 |
| |
| 3) EXTERIOR DOORS - FBC 3202.2ENCROACHMENTS ABOVE GRADE |
| AND BELOW 8 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT |
| OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| |
| 4) FLOOR PLAN AND LIFE SAFETY PLAN - THE FIRE RATED |
| ELEVATOR LOBBY AND CORRIDOR SEEMS NOT TO BE COMPLETE AT |
| HALL (107), MAIL BOX ROOM (115) AND TRASH ROOM (104) |
| ALONG WITH THE DOORS TO SUCH - PLEASE CLARIFY IF THE |
| FIRE WALL IS TO BE CONTINUOUS. |
| |
| 5) DRAWING A.501 SHOWS THE HANDRAIL EXTENSIONS AT THE |
| TOP LANDING TO TURN - HAND RAILS EXTENSIONS SHOULD NOT |
| TURN UNLESS THE STAIR CONTINUES - FBC 1014.6 WHERE |
| HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE |
| HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12 |
| INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO |
| SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM |
| RISER. |
| |
| 6) DRAWING A.501 PLYWOOD SHOWN ON THE EXTERIOR WALL |
| SHOULD BE SHOWN AS FIRE RETARDANT PER FBC 603.1 |
| |
| 7) PLEASE PROVIDE DETAILS FOR THE EXTERIOR WALL TILE |
| CLADDING - ATTACHMENTS SIZE, TYPE AND ON CENTER |
| SPACING, FRAMING ATTACHMENTS, WALL SHEATHING |
| ATTACHMENTS ETC. - OR PROVIDE PRODUCT APPROVALS - |
| EXTERIOR CLADDING IS SUBJECT TO WIND LOADS - FBC 1609.1 |
| |
| 8) PLEASE PROVIDE A SURVEY FBC WPB 107.1 |