Plan Review Notes For Permit 23030222 |
Permit Number |
23030222 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-06 10:33:55 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE DIMENSIONS FOR THE CANOPY - HEIGHT | | FROM GROUND, LENGTH AND WIDTH. FBC WPB 107.2.1 | | | | 2) PLEASE SHOW THE CANOPY DISTANCE FROM THE EDGE OF THE | | STREET CURB - FBC 3105.3.1.2 | | | | 3) DRAWING A6.01 SHOWS THAT SALVAGED STOREFRONT IS TO | | BE USED - PLEASE SHOW ALL ATTACHMENTS TO MEET THE WIND | | LOADS (FRAMING, GLAZING ETC.) - PLEASE PROVIDE A | | CURRENT PRODUCT APPROVAL FOR GLAZING IMPACT | | REQUIREMENTS OR PROVIDE THE SHUTTER PRODUCT APPROVALS. | | FBC 1609.1.2 | | | | 4) PLEASE PROVIDE A SURVEY - PROPERTY LINES NEED TO BE | | VERIFIED. FBC WPB 107.2.1 | | | | 5) DRAWINGS S0.01, S0.03, S1.02, S3.01 DO NOT SHOW AS | | DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|