2023-04-18 07:16:22 | 1ST REVIEW FMC |
| PERMIT: 23021503 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| MAIN HOUSE REVIEW: |
| |
| 1) THE MANUAL J CALCULATIONS PAGE 2 OF 10 FOR THE MAIN |
| HOUSE INDICATES A TOTAL COOLING LOAD OF 78,570 AND |
| 6.55-TONS FOR THE COMBINED UNIT SIZE FOR A TOTAL SQUARE |
| FOOTAGE OF 4,687. MANUAL J INDICATES THAT SYSTEM 1 IS A |
| 3.65-TON UNIT AND SYSTEM 2 REQUIRES A 2.90-TONS. SHEET |
| M.2 INDICATES SYSTEM 1 TO BE A 5-TON SYSTEM AND SYSTEM |
| 2 TO BE A 4-TON SYSTEM. PLEASE SHOW HOW EACH OF THESE |
| UNITS WILL MEET THE 1.15 TIMES GREATER THAN THE DESIGN |
| COOLING LOAD. FEC R403.7.1.2 |
| |
| 2) PLEASE ADD A NOTE TO SHEET M.1 INDICATING THAT THE |
| LOUVER FOR THE MAKE-UP AIR FOR THE HOOD SHALL BE |
| PROTECTED WITH A SCREEN. FRC R303.6 |
| |
| 3) SHEET M.2: PROVIDE AN EXHAUST FAN IN THE TUB AREA OF |
| THE PRIMARY BATH. FRC R303.3 |
| |
| GARAGE/GUEST HOUSE REVIEW: |
| |
| 1) THE GARAGE/GUEST HOUSE WILL REQUIRE A SEPARATE |
| PERMITS. |
| |
| 2) EXPLAIN THE ARROWS FROM EXTERIOR WALL TO MECHANICAL |
| UNIT IN ATTIC ABOVE KITCHEN. |
| |
| 3) INDICATE THE MOUNTING HEIGHT OF THE CONDENSING UNIT |
| BECAUSE OF THE FLOOD PLAIN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |