Plan Review Notes
Plan Review Notes For Permit 23021503
Permit Number 23021503
Review Stop E
Sequence Number 1
Notes
Date Text
2023-04-13 13:39:39FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW ELECTRICAL NOTES FOR NFPA 70 2017 EDITION.
  
 2. DISCONNECTING MEANS FOR A/C EQUIPMENT PER NEC 440.14
 OR IRC E4101.5
 DISCONNECTING MEANS ARE REQUIRED TO BE LOCATED
 ???WITHIN SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 3. THIS ELECTRICAL REVIEW IS ONLY FOR THE MAIN HOUSE.
 ACCESSORY STRUCTURE REQUIRES A SEPARATE PERMIT NUMBER.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  