2023-04-18 17:01:21 | SINGLE FAMILY RESIDENCE (R3)BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23021503 |
| 3408 WASHINGTON RD |
| |
| 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD |
| ZONE WITH THE BASE FLOOD BFE: 6 FEET BASED ON NAVD |
| 1988. |
| CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2) |
| FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC. |
| 18-284 CITY ORDINANCE NO. 4729-17). |
| DESIGNER OF RECORD NEEDS TO SPECIFY THE PROPOSED FINISH |
| ELEVATIONS, INCLUDING ALL EQUIPMENT SERVING THE TWO |
| BUILDINGS. |
| NOTE: MISSING INFORMATION FOR CONDENSING UNIT #3 AND |
| GUEST HOUSE EQUIPMENT. |
| |
| DURING THE PERMITTING/CONSTRUCTION OF THIS STRUCTURE |
| THREE DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE |
| REQUIRED (SEC. 107.3.5.1.1 CITY AMENDMENTS): |
| A) CONSTRUCTION DRAWINGS. |
| B) BUILDING UNDER CONSTRUCTION. |
| C) FINISHED CONSTRUCTION. |
| |
| NOTE: |
| NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION |
| CERTIFICATE NOW FOR REVIEW. |
| ALSO, NEED TO PROVIDE SURVEY AND FLOOD VENTS PRODUCT |
| APPROVAL SPECIFIED BY THE ARCHITECT TO VERIFY |
| ELEVATIONS AND NET FLOOD VENT NET AREA SPECIFIED ON |
| ELEVATION CERTIFICATE. |
| |
| 2-DESIGNER OF RECORD TO SPECIFY SIZE OF FLOOD VENTS. |
| SEC. R322.2.2 FBC-RESIDENTIAL. |
| |
| 3-FUTURE ELEVATOR: |
| A) FUTURE ELEVATOR LOCATION IS NOT CLEAR. INFORMATION |
| ON GROUND FLOOR FRAMING PLAN AND SECOND FLOOR FRAMING |
| PLAN INFORMATION DOESN'T MATCH INFORMATION ON PROPOSED |
| FIRST AND SECOND FLOOR PLANS. REVISE AS REQUIRED TO |
| MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) PROVIDE COMPLETE FRAMING DETAIL/SPECIFICATIONS FOR |
| FUTURE ELEVATOR CHASE. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| C)BASED ON BUILDING SECTION 1 ON SHEET A-7.1 THE |
| ELEVATOR EQUIPMENT WILL BE BELOW THE REQUIRED 2 FEET |
| FREEBOARD. COORDINATE WITH SEC. R322 FBC-RESIDENTIAL |
| FOR EQUIPMENT PROTECTION AND ENCLOSURE CONSTRUCTION. |
| |
| 4- SEPARATE PERMIT REQUIRED FOR THE EXISTING HOUSE |
| DEMOLITION. SEC. 1075.1 CITY AMENDMENTS. |
| |
| 5- SEPARATE PERMIT REQUIRED FOR THE RETAINING WALLS |
| SHOWN ON THE SITE PLAN. |
| 1075.1 CITY AMENDMENTS. |
| |
| 6- NEED BATHROOM #1 WITH A DOOR THAT PROVIDES 29" MIN. |
| CLEAR OPENING AS REQUIRED BY SEC. R320.1.1 |
| FBC-RESIDENTIAL. |
| |
| 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807 |
| FBC-RESIDENTIAL. |
| NOTE: THIS APPLIES TO BOTH BUILDINGS. |
| |
| 8- GUEST HOUSE ENTRY DOOR DOESN'T COMPLY WITH THE MIN. |
| CLEAR WIDTH OF 32" AS REQUIRED BY SEC. R311.2 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| 9-DRAFSTOPPPING DETAIL 1 ON SHEET A-2.1. CLARIFY HOW |
| PROVIDING 24X36 ACCESS PANELS ON THE FLOOR/CEILING |
| ASSEMBLY. SEE SIZE OF FLOOR TRUSSES SPECIFIED ON FLOOR |
| FRAMING PLAN. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR SELF-CLOSING PANEL ACCESS. |
| SEC. R302.12 FBC-RESIDENTIAL. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 10- EGRESS WINDOWS NOTE ON SHEET A-4.1 IS INCORRECT. |
| SEE SEC. R310.2.1 FBC-RESIDENTIAL AND REVISE AS |
| REQUIRED. |
| |
| 11- DOOR & WINDOW WIND PRESSURES TABLE ON SHEET S-5 |
| SPECIFY EXPOSURE C-180MPH WIND SPEED. ACCORDING TO SEC. |
| R301.2.1.4.3 FBC-RESIDENTIAL THIS BUILDING IS LOCATED |
| IN EXPOSURE "D" NOT "C". REVISE ALL WIND DESIGN |
| PRESSURES AS REQUIRED. |
| |
| 12-PLYWOOD SHEATHING NAILING SCHEDULE ON SHEET S-5 : |
| REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY |
| WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE |
| TYPE, SIZE AND SPACING. NOTE: NEED TO USE RING SHANK |
| NAILS. ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES |
| O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC. |
| R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| REQUIREMENTS. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 13- ENERGY CALCULATIONS (MAIN HOUSE): |
| A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, BUILDER'S NAME. SEC. |
| R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| C)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT. |
| PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS. |
| REVISE AS REQUIRED TO MATCH PLANS. IF TAKING THE |
| CEILING FAN CREDIT, THEN PLANS NEED TO SHOW CEILING FAN |
| AND SIZE IN ALL THE ROOMS AS REQUIRED BY TABLE R405.7.6 |
| FBC-ENERGY CONSERVATION |
| NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON |
| ROOM SIZE. |
| |
| D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| 14- ENERGY CALCULATIONS (GUEST HOUSE): |
| A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| C)ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN CREDIT. |
| PLANS DON'T SHOW CEILING FANS FOR ALL REQUIRED ROOMS. |
| REVISE AS REQUIRED TO MATCH PLANS. IF TAKING THE |
| CEILING FAN CREDIT, THEN PLANS NEED TO SHOW CEILING FAN |
| AND SIZE IN ALL THE ROOMS AS REQUIRED BY TABLE R405.7.6 |
| FBC-ENERGY CONSERVATION |
| NOTE: SEE SIZE AND NUMBER OF FANS REQUIRED BASED ON |
| ROOM SIZE. |
| |
| D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| 15- PRODUCT APPROVALS DEFERRED SUBMITTAL: AS REQUESTED |
| BY THE OWNER THE PRODUCT APPROVALS WILL BE SUBMITTED |
| LATER. |
| NOTE: SUBMIT FOR REVIEW AFTER THE PERMIT IS ISSUED BUT |
| BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. |
| A)EXTERIOR DOORS AS SHOWN ON PLANS. (NOTE: PLEASE |
| IDENTIFY EACH PRODUCT APPROVAL. FOR EXAMPLE ENTRY DOOR, |
| GARAGE SWING DOOR, ETC.) |
| B)WINDOWS AS SHOWN ON PLANS. |
| C)WINDOWS AND DOORS MULLIONS (NOTE: NEED TO SPECIFY |
| MULLION SIZE TO VERIFY PRESSURES. SEC. R301.2.1 |
| FBC-RESIDENTIAL). |
| D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| E)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| G)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE |
| PRODUCT APPROVAL. |
| H)HIP & RIDGE METAL SUPPORT TO BE USED. |
| L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE |
| TILE. |
| M)FLOOD VENTS SPECIFIED BY THE DESIGNER OF RECORD. |
| N)OVERHEAD GARAGE DOORS. |
| |
| 16- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 17- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS |
| SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC |
| EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO |
| VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| NOTE: THIS COULD BE A DEFERRED SUBMITAL ALSO. |
| |
| 18- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| |
| 19- SPECIFY CARBON MONOXIDE ALARMS BY ALL BEDROOMS AS |
| REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL. |
| NOTE: GUEST SUITE NEEDS ONE. |
| |
| 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| PERGOLAS OR TRELLIS SHOWN ON THE MAIN HOUSE AND |
| SEPARATE GUEST HOUSE. SPECIFY ALL FRAMING MEMBERS AND |
| CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 21- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING |
| THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS |
| AND THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE |
| GARAGE, ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY |
| CONSERVATION. |
| NOTE: SECTION 1 ON SHEET A-7.2 DOESN'T SHOW INSULATION |
| ABOVE GARAGE. |
| |
| 22- HANDRAILS AND GUARDRAILS: DESIGNER OF RECORD TO |
| PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS AS |
| REQUIRED BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 |
| FBC-RESIDENTIAL. |
| (SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT DESIGN |
| DETAILS AND SPECIFICATIONS ARE MET). |
| NOTE: GUARDRAIL SECTIONS/DETAILS ON SHEETS A-6.3, |
| A-7.1,A-7.2, A-7.3 SHOW 4" DIMENSION AT THE BOTTOM OF |
| THE GUARDRAIL. THIS DOESN'T COMPLY WITH THE REQUIREMENT |
| THAT A 4" SPHERE CANNOT PASS THRU. REVISE AS REQUIRED. |
| ALSO, A 6" SPHERE CANNOT PASS THRU THE TRIANGULAR |
| OPENINGS ON THE STAIRS. PROVIDE INFORMATION AS |
| REQUIRED. |
| |
| 23- SHEET C-1: ENGINEER DIGITAL SIGNATURE DOESN'T SEEM |
| TO COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. |
| IT DOESN'T HAVE A TITLE BLOCK, THE REQUIRED TEXT BOX |
| LANGUAGE. IT ONLY SHOWS DIGITALLY SIGNED BY RICHARD V |
| REIKENIS AND THE DATE. IT DOESN'T IDENTIFY THE |
| ENGINEER'S LICENSE NUMBER. |
| SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING |
| AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS AND RESUBMIT |
| DRAWING WITH VERIFIABLE DIGITAL SIGNATURE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |