Plan Review Notes
Plan Review Notes For Permit 23021442
Permit Number 23021442
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-02 11:06:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A PROPOSED NEW STORAGE
 ROOM WITH 2-HOUR RATED WALLS; HOWEVER, THERE IS NO
 INDICATION OF A FIRE RATED DOOR ASSEMBLY TO THIS ROOM.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE A RATED DOOR ASSEMBLY EQUAL TO PROPOSED
 RATED WALLS.
  
  
 2) THERE IS NO INDICATION OF WHAT IS BEING PROPOSED TO
 STORE WITHIN THIS STORAGE ROOM
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE DETAILS ON THE PROPOSED STORAGE
 MATERIALS/COMMODITY/HAZARD CLASSIFICATIONS.
  
  
 3) THERE IS NO INDICATION OF THE RACKS/SHELVING TYPE,
 LOCATION AND HEIGHT BEING USED IF ANY.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE DETAILS OF THE RACKS/SHELVING TYPE,
 LOCATION AND HEIGHT.
  
  
 4) THERE IS NO INDICATIONS OF EXISTING FIRE SPRINKLER
 PROTECTION.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS
 EXISTING FIRE SPRINKLER PROTECTION.
  
  
 5) THERE IS NO INDICATIONS OF EXISTING FIRE ALARM
 PROTECTION.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS
 EXISTING FIRE ALARM PROTECTION AND THE LOCATION OF ANY
 DEVICES WITHIN THIS ROOM.
  
  
 6) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AS TO WHAT
 SYSTEM MAYBE EXISTING.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  