2023-03-24 16:54:23 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 23021413 |
| 3/24/23 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS G101 1394 & 1306: I HAVE RESEARCHED THE WPB |
| BUILDING DEPT. RECORDS AND WAS UNABLE TO LOCATE A |
| PERMIT FOR THE EXISTING GAS WATER HEATERS AND RANGES |
| FOR THE APARTMENTS. THE PROPOSED REPLACEMENTS WILL HAVE |
| TO BE REVIEWED AS NEW INSTALLATIONS SINCE THERE ARE NO |
| PREVIOUS GAS PIPING PLANS ON FILE TO REFERENCE. PLEASE |
| PROVIDE THE FOLLOWING DRAWINGS AND DETAILS IN |
| ACCORDANCE WITH SECS. 107.2.1 AND 107.3.5.3 WPB. |
| |
| 2) GAS PLANS AND RISER DRAWINGS FOR EACH APARTMENT |
| SHOWING ALL EXISTING AND NEW GAS PIPING AND APPLIANCES. |
| PLEASE INCLUDE A FLOOR PLAN DRAWING SHOWING THE |
| APPLIANCE LOCATIONS AND GAS PIPING RUNS THROUGH THE |
| BUILDINGS. THE RISER SHALL INCLUDE- |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURES AT EACH METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METERS |
| TO THE MOST REMOTE APPLIANCE OUTLETS. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS AND OUTLET PRESSURES. |
| H) LOCATIONS OF SHUTOFF VALVES. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 3) PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER |
| HEATERS LISTING THE MAKES, MODELS AND BTU CAPACITIES- |
| SEC. 624,1 FBC FG. |
| |
| 4) PROVIDE COMBUSTION AIR AND VENTING PLANS FOR THE |
| WATER HEATERS- SECS. 304.1, 503.1, & 624.1 FBC FG. |
| |
| 5) PROVIDE COMBUSTION AIR AND EXHAUST VENTILATION PLANS |
| FOR THE RANGES- SEC. 304.1 FBC FG & SEC. 505 FBC |
| MECHANICAL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |