Plan Review Notes
Plan Review Notes For Permit 23021392
Permit Number 23021392
Review Stop G
Sequence Number 2
Notes
Date Text
2023-03-10 08:08:252ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23021392
 3/10/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISO #2: INCREASE THE SIZE OF ??-INCH GALVANIZED
 PIPE SUPPLYING THE RANGE TO ??-INCH- TABLE G2413.4(1)
 FBC RES.
  
 2) THE RESUBMITTED RISER DRAWING IS MISSING THE PIPING
 TO THE DRYER. A COMPLETE RISER DRAWING IS REQUIRED-
 SEC. 107.3.5.3 WPB.
  
 3) COMBUSTION AIR CALCULATIONS FOR THE GAS RANGE AND
 DRYER NOT PROVIDED- SEC. G2407.1 FBC RES. PLEASE NOTE
 THAT IF USING THE STANDARD METHOD OF INDOOR AIR FOR THE
 RANGE IN ACCORDANCE WITH SEC. G2407.5.1, A TOTAL VOLUME
 OF 6250 CU. FT. IS REQUIRED. PLEASE PROVIDE A BASIC,
 DIMENSIONED FLOOR PLAN DRAWING SHOWING THE LOCATIONS OF
 BOTH THE RANGE AND THE DRYER AND PROVIDE THE
 CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  