Plan Review Notes For Permit 23021392 |
Permit Number |
23021392 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-03-10 08:08:25 | 2ND REVIEW FBC-2020 RES. GAS | | PERMIT- 23021392 | | 3/10/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS ISO #2: INCREASE THE SIZE OF ??-INCH GALVANIZED | | PIPE SUPPLYING THE RANGE TO ??-INCH- TABLE G2413.4(1) | | FBC RES. | | | | 2) THE RESUBMITTED RISER DRAWING IS MISSING THE PIPING | | TO THE DRYER. A COMPLETE RISER DRAWING IS REQUIRED- | | SEC. 107.3.5.3 WPB. | | | | 3) COMBUSTION AIR CALCULATIONS FOR THE GAS RANGE AND | | DRYER NOT PROVIDED- SEC. G2407.1 FBC RES. PLEASE NOTE | | THAT IF USING THE STANDARD METHOD OF INDOOR AIR FOR THE | | RANGE IN ACCORDANCE WITH SEC. G2407.5.1, A TOTAL VOLUME | | OF 6250 CU. FT. IS REQUIRED. PLEASE PROVIDE A BASIC, | | DIMENSIONED FLOOR PLAN DRAWING SHOWING THE LOCATIONS OF | | BOTH THE RANGE AND THE DRYER AND PROVIDE THE | | CALCULATIONS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|